Model 1093A/B/C
GPS Satellite-Controlled Clock
Specifications
|
Receiver Characteristics:
- Timing Accuracy:
-
Specifications apply at the
1 PPS output, in the presence of Selective Availability (SA), as
of date of publication.
-
UTC/USNO:
±1 µs peak
- Position Accuracy:
-
-
25 meters, USA Department
of Defense Selective Availability (SA) off.
-
100 meters, Selective
Availability on.
-
Altitude, 140 meters,
Selective Availability on.
-
All specifications rms,
95% confidence, with Position-Hold Mode off and receiving at
least four satellites
- Satellite Tracking:
-
Twelve (12) channel, C/A
code (1575.42 MHz). Receiver simultaneously tracks up to twelve
satellites. Results from all tracked satellites are averaged in
Position-Hold Mode or, with Position-Hold Mode off, using
least-squares estimation.
- Acquisition:
-
-
2 minutes typical, cold
start
-
15 minutes, 90%
confidence, cold start
-
40 seconds, 90%
confidence, with almanac less than 1 month old
-
15 seconds, 90%
confidence, with ephemeris less than 4 hours old
-
The GPS Data Backup
Battery is now included in the Model 1093A/B/C. This feature
improves acquisition time to as little as 15 seconds after a
brief power loss by supplying constant power to the real-time
clock and RAM in the GPS receiver module.
|
I/O Configuration:
- Connectors:
-
Two standard:
one IRIG-B Unmodulated and one 1 PPS; Type: bus driver, 5 V CMOS;
10 ohms source impedance; ±75 mA drive capability; pluggable
terminal strip.
-
Open-drain FET
drivers (400 V, 220 mA, 1 W power dissipation) can also
be fitted; contact factory.
- Event A Input:
-
One event timer channel with
1 µs resolution is standard. This function may be driven by the
start bit of a received character on the serial port, or (by
internal connection) an external 5 V CMOS/TTL signal at one of the
terminal strip connectors.
- Programmable Pulse Output:
-
One programmable output
pulse (by a jumper connection) that may be output on a terminal
strip connector or the AUX OUT pin on either RS-232 Port.
-
Four modes:
-
Every 1 to 60,000 seconds,
starts top of the minute
-
Hourly at a specified
offset
-
Daily at a specified time
of day
-
One shot at a specified
time of year
-
Pulse duration is
programmable from 0.01 to 600 seconds, except in one-shot mode,
where the output is Low prior to the specified time and High
thereafter.
- I/O Options:
-
IRIG-B Modulated
(1093opt92): bus driver, 4 Vpp, 20 ohms source impedance; drives a
50-ohm load at 3 Vpp; pluggable terminal strip
-
Second RS-232 Port
(1093opt19): Provides all the same capabilities as the standard
RS-232C serial port except there is no AUX IN line. AUX OUT
provides programmable pulse function at RS-232 levels.
-
Relay contacts (1093opt93):
1 set, Form C (SPDT) fail-safe, 0.3 A at 130 Vdc; Locked function.
|
Interface:
- Operator:
-
Display:
-
Status LEDs (Models
1093A/B/C)
-
2 x 20 character
supertwist LCD (Model 1093B/C)
-
14 mm (0.56 in.) LED; 9
digits (Model 1093C)
-
Functions:
-
Time: UTC or local
-
Position: latitude,
longitude, altitude
-
Receiver and clock status
-
1 PPS (input) deviation
-
Event time
-
Status LEDs:
-
Operate (green)
-
Unlocked (red)
-
Keypad:
Eight keys; select display functions or setup menus (Model
1093B/C)
-
Setup:
-
Local time offset
-
Output code select:
Local/UTC
-
Daylight Saving Time (Set
Summer Time): Off/On/Auto USA/Auto EUR/Auto CUS
-
Backlight control:
On/Off/Auto
-
Event input: Event/1 PPS
-
Programmable Pulse setup
-
Antenna delay
-
Out of lock time: 1 to 99
minute(s), Off, or Zero Delay
-
Auto-Survey: On/Off,
Survey duration
-
Position Hold: On/Off,
Position Auto/Manual
-
Option Configuration and
Setup
-
Serial port: RS-232
- System:
-
RS-232:
1200 to 19,200 baud; 7 or 8 data bits; 1 or 2 stop bits;
even/odd/no parity
-
Interrogate mode
-
Broadcast modes:
-
Standard ASCII (IRIG-J)
-
Extended ASCII
-
ASCII with Time Quality
-
ASCII with Time Quality
and Year
-
Vorne large-display time
-
Status/Alarm
-
Event data
-
Connector:
Male 9-pin D-sub (TXD, RXD, AUX IN, AUX OUT)
-
AUX OUT
can provide programmable pulse function at RS-232 levels
-
RS-422/485
driver can also be fitted (1093opt94)
-
Second RS-232 port
available (1093opt19)
-
Connector:
Male 9-pin D-sub (TXD, RXD)
|
Power Requirements:
- Standard:
-
Voltage:
85 to 264 Vac, 47 to 440 Hz, 20 VA maximum or 110 to 275 Vdc, 15 W
maximum.
Inlet: IEC-320 with fuse and mating cordset. Specify
option P01 - P10.
-
General:
- Physical:
-
Size: 1 RU
rack mount or tabletop, 260 mm deep FMS, Rack mounts included
Weight: 2 kg (4.5 lbs), net; 8 kg (17 lbs), shipping
- Antenna:
-
Mounting:
0.75 in. pipe (1 in. - 14 marine) thread
Cable Connection: F-type
Size: 77.5 dia. x 66.2 mm (3.05 x 2.61 in.)
Weight: 170 grams (6.0 oz)
- Antenna Cable:
-
Type:
RG-6, 15 m (50 ft) provided
Weight: 0.69 kg (1.52 lbs) per 15 m
- Environmental:
-
Operating
Temperature: 0° to +50° C (-20° to +70° C typical)
Non-operating Temperature: -40° to +75° C
Humidity: Non-condensing
EMC: Radiated susceptibility: passes
walkie-talkie test. Conducted emissions: power supply
complies with FCC 20780, Class A and VDE 0871/6.78 Class A.
Surge withstand capability (SWC), power inlet: designed to
meet ANSI/IEEE C37.90-1 and IEC 801-4.
|
|