Specifications
     

The Arbiter Systems®, Inc. Model 928A Power System MultimeterTM has two identical measurement channels, Channel A and Channel B. Each input channel has a voltage input and a current input. Current inputs are intended for use with external CTs having a nominal output of 0 to 1 Arms or 0 to 1 Vrms. For basic measurements (voltage, current, frequency, and phase angle) any combination of inputs may be used. For power and energy measurements (active power, apparent power, reactive power, and power factor), one voltage and one current must be selected.
 

Input Configuration
 
  Voltage:  
  Input Range

0 to 660 Vrms

  Impedance

1.2 megohm, differential

     
 

Current:

 
  Input Range

0.01 to 1 Arms (underrange to < 1 mA) (or 0 to 1.2 Vrms)

  Burden

0.01 ohm maximum (current input style) or 100 kohms nominal (voltage input style)

     
Interface
     
 

Operator Interface:

  Display

128 x 64 graphic LCD

  Keyboard

30 key keypad

  Serial 

USB

  Memory

512 KB flash

  Data

User setups, Real Time Clock, Approximately 400 KB measurement data

     
Power Requirements
     
 

Batteries (not included):

  Type

4-AA Cells, alkaline or NiMH

  Operation

30 hours typical with alkaline cells. 60 hours typical with NiMH

 

External (not included):

  Type

+7 Vdc, unregulated

  Current

< 100 mA

  Connector

5.5 x 2.0 mm, center positive

     
Measurements
     
 

Voltage:

  Method 

Wideband: True rms, 3 kHz Bandwidth, Narrowband: Fundamental magnitude

  Accuracy

0.1% of reading

 

Current:

 
  Method

Wideband: True rms, 3 kHz Bandwidth, Narrowband: Fundamental magnitude

  Accuracy

0.1% of reading (current),

   

1% of reading (low current range)

 

Phase Angle, A-B:

  Range

0 to 360° or ±180°

  Accuracy

0.1°

   

Underrange < 1° typical

 

Frequency:

  Range

50 or 60 Hz ±5 Hz

  Accuracy

0.005% of reading

 

Harmonics:

 
  Input

Channel A and Channel B, simultaneous

  Range

2nd to 50th Harmonic (50 or 60 Hz fundamental)

  Accuracy

0.1% THD +5% reading

  Display
 

THD; K-factor; Amplitude bar graph; and individual harmonic magnitude and phase (simultaneous)

  Waveform:  
  Display

Channel A and/or Channel B

 

 

Power  
     
 

Power / Energy Quantities:

  Range

0 to 99999 MVA or MVAh

   

±99999 MVAR or MVARh

   

±99999 MW or MWh

   

±1.0000 PF, lead or lag

  Accuracy

0.1% of VA, for VA, VAR, and W 0.001 PF

     
Physical  
     
 

Dimensions:

  Size

196mm x 101mm x 38 mm (7.75" x 4" x 1.5")

 

Weight:

 
  Weight

1 kg (2.2 lbs.), maximum

     
Environmental
  Temperature:
  Operating

-10° to +50° C

  Non-operating

 -40° to +75° C

  Humidity

Non-condensing

 

 

Accles & Shelvoke| Aqua-Tronics | Arbiter Systems | Clare Instruments | Haefely | Hipotronics | HV Diagnostics | Megger | Tettex | T & R Equipment  
Home Page | High Current | High Voltage | Cable Fault | Oil Test | Transformer | Insulation 

 
Macey's Electrical Pty Ltd
ABN 17 344 601 468
Unit 1, 49 Gavenlock Road,  Tuggerah,  Sydney  Australia  2259

 

Phone: 61 2 4353 4644 

Mobile: 0412 678 925

Fax: 61 2 4353 4424

mailto:sales@maceyselectrical.com.au
 

Copyright: 1978 to 2007                                                   Last update: Friday, 03 October 2008