Specifications/Measurement Functions

           
Earth/Ground Bond Insulation Resistance
 

Test Voltage:

12V AC nominal  

Test Voltage:

200V-1050V DC, 5V steps
 

Test Current:

0-26A, 1A steps

Measurement Range:

0-20MΩ, in 10kΩ steps.

Measurement Range:

0-1.999Ω,     19MΩ-199.99MΩ, in
    resolution 0.001Ω     0.1MΩ steps
 

Test Time:

0-255 Seconds, in  

Test Time:

0-255 Seconds, in
    1 Second steps     1 Second steps

Measurement System:

4 Wire      
           
AC Flash/Hipot DC Flash/Hipot
 

Test Voltage:

100V-5kV AC, 25V steps  

Test Voltage:

200V-6kV DC, 25V steps
 

Test Current:

20mA AC max  

Test Current:

10mA DC max

Measurement Range:

0-19.99mA, resolution

Measurement Range:

0-9.99mA, resolution
    0.01mA     0.01mA
 

Ramp Time:

0.5-25 Seconds, in  

Ramp Time:

0.1-25 Seconds, in
    0.1 Second steps      0.1 Second steps
 

Dwell Time:

0-255 Seconds, in  

Dwell Time:

0-255 Seconds, in
    1 Second steps     1 Second steps
           
Phase Neutral Continuity Earth Leakage
 

Test Voltage:

9V DC nominal  

Test Voltage:

100V-300V, 1V increments
 

Test Current:

8mA DC  

Test Current:

10mA max

Measurement Range:

0-1999Ω, resolution 1Ω

Measurement Range:

0-9.99mA, resolution 0.01mA
 

Test Time:

0-255 Seconds, in  

Test Time:

0-255 Seconds, in
    1 Second steps     1 Second steps
           
Load/Function Earth Continuity
 

Test Voltage:

10V-280V, 1V increments  

Test Voltage:

250mV DC max
    (E9024V)  

Test Current:

100mA DC constant current
 

Test Current:

10A AC max (E9024V)

Measurement Range:

0-1.999Ω, resolution 0.001Ω
    16A AC max (E9024)  

Test Time:

0-255 Seconds, in
 

Test Time:

0-255 Seconds, in     1 Second steps
    1 Second steps  

Measurement:

4 wire
       

System:

 
           
Analogue Test Features

Voltage Input Range:

0-10V   Electronic storage

Measurement Range:

0-11.99V, resolution 0.01V  

of test results:

Yes
 

Test Time:

0-255 Seconds, in  

Test sequences:

Predefined and Custom
    1 Second steps  

Visual alarm:

Yes
           
External Connections Environment
 

COMM1:

RS232 DTE  

Dimensions:

520mm x 210mm x 400 mm
 

COMM2:

RS232 DCE     approx.
 

Control Port:

16 way cage clamp  

Weight:

45kg
    connector  

Standards:

Conforms to EN61010,
 

Digital Port:

16 way cage clamp     EN50081-1, EN50082-2
    connector  

Supply Voltage:

110V/230V 50/60Hz
 

Keyboard:

PS2 socket

EN50191 compliant:

Yes (when used with certain
          accessories)

 

 

Accles & Shelvoke| Aqua-Tronics | Arbiter Systems | Clare Instruments | Haefely | Hipotronics | HV Diagnostics | Megger | Tettex | T & R Equipment  
Home Page | High Current | High Voltage | Cable Fault | Oil Test | Transformer | Insulation 

 