Self-Contained Unit Features
Proof Tester, Burner and Thumper in One.
Burn Currents to 50 mA.
Impulse Energies of up to 900
J.
Automatic and Manual Thumper
Mode.
Operable from Line Voltage or
Generator.
Single HV Output for All Modes.
Zero Start Interlock.
External Interlock.
Mode Indicator Lights.
Electrically Operated Shorting
Solenoids with Mechanical Ground Assurance.
Benefits
Accurate Fault Identification
and Location.
One Unit for all URD Cable
Maintenance Testing.
User Safety - visual
verification of grounding status via face panel window.
Repeatable Impulse level.
Variable Impulse Rate from 3 to
30 Seconds.
Applications
Electrical Utilities.
Test Companies.
Petrochemical Facilities.
Facility Maintenance.
Description Hipotronics CF Series
test systems for fault locating of primary cables consist of a
dc proof tester, a burner and a capacitive discharge fault
locator (thumper). These self-contained, portable units are
rugged, reliable and compact making them ideal for field use.
The CF30-8 has a continuously adjustable impulse rate from
three to thirty seconds. Test ratings are a 30 kV dc proof
test voltage, a 50 mA burn current and a 0-15 kV dc capacitive
discharge (thumper) voltage.
The units can be used
with a high voltage coupler (4100 Series) and a time domain
Reflectometer (TDR) to quickly provide a specific distance to
the fault in feet or meters. This combination of equipment can
greatly reduce the amount of high voltage (number of thumps)
the cable resulting in reduced damage or degradation to the
cable under test.
For additional
pinpointing the HSDAD acoustical detector can be used in
conjunction with the CF30-8 to pinpoint the exact underground
location. While the CF “thumps” the cable the user “listens”
to the thumping using HSDAD and can pinpoint where to start
digging to repair the fault.
Specifications
Model Number
CF30-8
Input Voltage
Model
No. suffix -A
115 volts AC, 60Hz, 2kVA
Model
No. suffix -B
230 volts AC, 50/60Hz,
2kVA
Output
Proof Tester
0 to 30kV DC
(continuously variable)
Burn Current
50mA
Capacitor Discharge
0 to 15kV at 8µF
Energy Delivered to
Fault
900 Joules
Metering
Proof
Test Voltage
0 to 30kV DC, ±2%
Proof
Test Current
0 to 1mA, 10mA, 50mA DC,
±2%
Burner Current
0 to 50mA
Duty Cycle
Continuous (7 pulses per
minute)
Terminations
Input
Line
10 feet (3.1m) cable
Return
and High Voltage
50 feet (15.2m) shielded
cable with vise grip terminations
16" (W) x 30" (H) x 16"
(D) 406mm (W) x 762mm (H) x 406mm (D)
Weight
Net
185 lbs (85kg)
Shipping
250 lbs (128kg)
Scope of Supply
Qty. 1
CF30-8 with terminations as
described above.
Qty. 1
Interlock Plug PN800661
Qty. 1
Operations Manual
Qty. 1
Calibration Certificate
Ordering Information
Model
Description
CF30-8-A
Cable Fault Locator System (115
volts AC, 60Hz, 2kVA)
CF30-8-B
Cable Fault Locator System (230
volts AC, 50/60Hz, 2kVA)
CF30-8-PT-A
Cable Fault Locator System (115
volts AC, 60Hz, 2kVA), with only 15 feet of return and HV
cable and MC type connector for use with HVC coupler and 8100
cable rack.
CF30-8-PT-B
Cable Fault Locator System (230
volts AC, 50/60Hz, 2kVA), with only 15 feet of return and HV
cable and MC type connector for use with HVC coupler and 8100
cable rack.
Optional Accessories
Part Number
Description
SPK1-CF30-8
Spare parts kit for CF30-8
TDR1150
Time Domain Reflectometer
HVC4100
Series
HV coupler to protect TDR from HV of
cable fault locator. TDR must be used with coupling device.
8100
HV Cable Rack with 125 ft of 70kV
cable and 125 ft of safety ground cable.