Proof tester, burner, thumper
in one self-contained unit.
Burn currents to 100 mA.
Impulse energies of 3750 J to
7500 J.
Automatic and manual thumper
mode.
Operable from line voltage or
generator.
Single HV output for all modes.
Isolated and shielded return
current path.
Zero start interlock.
External interlock.
Face panel window.
Mode indicator lights.
Electrically operated shorting
solenoids with mechanical ground assurance.
Internal radar pickup for Model
M602TDR
Benefits
Positive fault identification
and location.
Isolated return for increased
operator safety.
One unit for all URD cable
maintenance testing.
Visual ground verification.
Precise impulse repetition.
Variable impulse rate from 3 to
30 seconds.
Description Hipotronics CF Series
testing systems for fault locating of primary cables consist
of a dc proof tester, a burner and a capacitive discharge
fault locator (thumper). These self-contained, portable units
are rugged, reliable and compact. All models feature a
continuously adjustable impulse rate from three to thirty
seconds.
70 kV dc proof
tester.
100 mA burner.
0-25 kV dc thumper.
Operates from 120 V
ac line or portable generator (220 V ac is available as an
option).
Model CF70-12 is a 25
kV, 12mF thumper and the CF70-24 is a 25kV, 24 mF thumper.
Both units combine a 70 kV dc proof tester, a 100 mA burner
and a capacitive discharge fault locator (thumper). Absolute
accuracy of the impulse repetition rate is achieved by using a
unique, motorized spark gap. Each unit also has an internal
radar pickup for the Model M602TDR.
Specifications
Input
Voltage
Model
No. suffix -A
115 volts AC, 60Hz
Model
No. suffix -B
230 volts AC, 50/60Hz
Output
CF70
Proof Tester
Continuously
variable to 70kV DC, 0 to 60kV above 5000 ft. altitude
Burner
100mA
Capacitor Discharge
Model
CF70-12
Model
CF70-24
0 to 25kV
at 12µF
0 to 25kV
at 24µF
Energy Delivered to
Fault
3750
Joules
7500
Joules
Metering
CF70
Proof Test Voltage
0 to 70kV DC, ±2%
Proof
Test Current
0 to 1mA, 10mA,
100mA DC,
±2%
Burner
Current
0 to 100mA
Duty Cycle
Continuous
Terminations
CF70 Input Line
50 feet
(15.2m) cable
Return and High
Voltage
100 feet
(30.4m) double shielded cable
Ground
25 feet
(7.6m) N0.2 welding cable
Dimensions and Weight
Model
CF70-12
Model
CF70-24
Dimensions
16" (W) x
36" (H) x 36" (D)
16" (W) x
36" (H) x 50" (D)
41cm (W)
x 91cm (H) x 91cm (D)
41cm (W)
x 91cm (H) x 127cm (D)
Net
Weight
540 lb
(246kg)
675 lb
(307kg)
Shipping Weight
750 lb
(341kg)
894 lb
(352kg)
Ordering Information
Model
Description
CF70-12-A
Cable Fault Locator System (115
volts AC, 60Hz)
CF70-12-B
Cable Fault Locator System (230
volts AC, 50/60Hz)
CF70-24-A
Cable Fault Locator System (115
volts AC, 60Hz)
CF70-24-B
Cable Fault Locator System (230
volts AC, 50/60Hz)