Macey's Electrical Logo

Hubbell logo Hipotronics logo

Cable Fault Test Equipment

 TDR-1150 Digital Time Domain Reflectometer

 

You are here:   TDR-1150 Cable Fault Locator 
Navigation:  Cable Fault Tester Index Hipotronics Equipment Index > TDR cable fault steps
The TDR 1150 can be used on a wide variety of capacitive discharge devices, commonly called “thumpers.” A high voltage coupler  is required as an interface between the TDR and the thumper.
Features
  • Step-by-step on screen instructions.
  • Automatic placement of start, end, and fault cursors.
  • Automatically tells the operator the cable length and distance to the fault.
  • Clear and easy-to-read wave shapes on large color screen.
  • “Basic and Advanced” modes.
  • Saves up to 16 three phase cable traces and 16
    user-defined test profiles.
  • Password protection of TDR adjustments.
  • Multiple languages.
  • RS232 port for downloading traces or upgrading
    software.

Benefits

  • Operational on a wide variety of “thumpers”.
  • Prolongs cable life.
  • Ideal for sectionalizing.
  • Restores service to customers faster.
 
Description of Operation

The TDR 1150 can be used on a wide variety of capacitive discharge devices, commonly called “thumpers.” A high voltage coupler (also available from Hipotronics) is required as an interface between the TDR and the thumper.

Basic Mode of Operation
Basic mode provides the simplest mode of operation for pre-locating most cable faults. It provides step-by-step instructions and prompts the operator through the operation of the TDR and thumper.

The auto range feature fits the cable trace on the screen, regardless of the cable length. The TDR automatically sets the “Start” and “End” cursors, and provides a numeric value for the cable length.

The operator is then prompted to send a single high voltage pulse down the cable. The TDR displays the high voltage trace and places a fault cursor at the point of the fault, and displays the distance to the fault. There is no need to interpret traces or move cursors. The entire process can be completed within minutes. Training time is significantly reduced.

Advanced Mode of Operation
In Advanced Mode, the operator has complete control of the TDR functions and settings. It is password protected to prevent unauthorized use. This mode provides more experienced operators with the diagnostic tools they need to find more difficult faults.

TDR functions that can be adjusted include: propagation velocity, pulse width, gain, 3 phase or single phase display, and trigger delay. They also have the ability to move cursors and adjust screen size (zoom). Memory functions, measuring units, language choices, the option to reset defaults, and much more are accessible in this mode.

 
 
Specifications
Power Supply 100V to 240 Volts AC, 50/60Hz or 12 volts DC
Operating System WindowsTM
Language Modes English, Spanish, Portuguese (user selectable in advanced mode)
Thumper Options 5150, CET, CF70, CF30, Generic Thumper
Units Feet, Yards, Meters (user selectable in advanced mode)
Measuring Range 1 ft to 160,000 feet
Accuracy 1% of total cable length
Pulse

Amplitude

25 volts into 50 0hms

Width
 

50ns, 100ns, 200ns, 500ns, 1µs, 2µs, 5µs, 10µs,
(user selectable in advanced mode)
Sample Rate 12.5MHz to 100MHz (user selectable in advanced mode)
Trigger Delay 1ms to 30ms (user selectable in advanced mode)
Screen 10.4" VGA color
Memory Modes

Trace

32 sets of 1 or 3 phase cable traces (user selectable in advanced mode)

Setup

16 setup options (user selectable in advanced mode)

RS232 Port

Download traces to PC and make upgrades (user selectable in advanced mode)
Dimensions 17.5" (W) x 12" (H) x 7" (D)   
445mm (W) x 305mm (H) x 178mm (D)
Weight 18 lbs   (8.2kg)
Environmental

Operating Temperature

0°C to 50°C   (32°F to 122°F)

Storage Temperature

-40°C to 60°C   (-40°F to 140°F)
 
 
Ordering Information
Model Number Description
TDR-1150 Portable Computer Based, Digital Cable radar (TDR) Color LCD, ARC Reflection, Low Voltage Direct and Serial Port.
TDR-1150-RTRFT Retrofit Kit upgrade CDI and Hipotronics First Response with New TDR 1150. Includes: 1150, all necessary cable connections, CFFR and charging circuit modifications, instruction modification book.
Power Supply 100V to 240 Volts AC, 50/60Hz or 12 volts DC
1150-PS Power Supply 100V to 240 Volts AC, 50/60Hz input (for use when not connected to the First response).


 

Accles & Shelvoke| Aqua-Tronics | Arbiter Systems | Clare Instruments | Haefely | Hipotronics | HV Diagnostics | Megger | Tettex | T & R Equipment  
Home Page | High Current | High Voltage | Cable Fault | Oil Test | Transformer | Insulation 

 
Macey's Electrical Pty Ltd
ABN 17 344 601 468
Unit 1, 49 Gavenlock Road,  Tuggerah,  Sydney  Australia  2259

 

Phone: 61 2 4353 4644 

Mobile: 0412 678 925

Fax: 61 2 4353 4424

mailto:sales@maceyselectrical.com.au
 

Copyright: 1978 to 2007                                                   Last update: Friday, 03 October 2008