Automatic placement of start,
end, and fault cursors.
Automatically tells the
operator the cable length and distance to the fault.
Clear and easy-to-read wave
shapes on large color screen.
“Basic and Advanced” modes.
Saves up to 16 three phase
cable traces and 16 user-defined test profiles.
Password protection of TDR
adjustments.
Multiple languages.
RS232 port for downloading
traces or upgrading software.
Benefits
Operational on a wide variety
of “thumpers”.
Prolongs cable life.
Ideal for sectionalizing.
Restores service to customers
faster.
Description of Operation
The TDR 1150 can be
used on a wide variety of capacitive discharge devices,
commonly called “thumpers.” A high voltage coupler (also
available from Hipotronics) is required as an interface
between the TDR and the thumper.
Basic
Mode of Operation Basic mode provides the
simplest mode of operation for pre-locating most cable faults.
It provides step-by-step instructions and prompts the operator
through the operation of the TDR and thumper.
The auto range
feature fits the cable trace on the screen, regardless of the
cable length. The TDR automatically sets the “Start” and “End”
cursors, and provides a numeric value for the cable length.
The operator is then
prompted to send a single high voltage pulse down the cable.
The TDR displays the high voltage trace and places a fault
cursor at the point of the fault, and displays the distance to
the fault. There is no need to interpret traces or move
cursors. The entire process can be completed within minutes.
Training time is significantly reduced.
Advanced
Mode of Operation In Advanced Mode, the
operator has complete control of the TDR functions and
settings. It is password protected to prevent unauthorized
use. This mode provides more experienced operators with the
diagnostic tools they need to find more difficult faults.
TDR functions that
can be adjusted include: propagation velocity, pulse width,
gain, 3 phase or single phase display, and trigger delay. They
also have the ability to move cursors and adjust screen size
(zoom). Memory functions, measuring units, language choices,
the option to reset defaults, and much more are accessible in
this mode.
Specifications
Power Supply
100V to 240 Volts AC,
50/60Hz or 12 volts DC
Operating System
WindowsTM
Language Modes
English, Spanish,
Portuguese (user selectable in advanced mode)
Thumper Options
5150, CET, CF70, CF30,
Generic Thumper
Units
Feet, Yards, Meters
(user selectable in advanced mode)
12.5MHz to 100MHz (user
selectable in advanced mode)
Trigger Delay
1ms to 30ms (user
selectable in advanced mode)
Screen
10.4" VGA color
Memory Modes
Trace
32 sets of 1 or 3 phase
cable traces (user selectable in advanced mode)
Setup
16 setup options (user
selectable in advanced mode)
RS232 Port
Download traces to PC
and make upgrades (user selectable in advanced mode)
Dimensions
17.5" (W) x 12" (H) x 7"
(D)
445mm (W) x 305mm (H) x
178mm (D)
Weight
18 lbs
(8.2kg)
Environmental
Operating
Temperature
0°C
to 50°C (32°F
to 122°F)
Storage Temperature
-40°C
to 60°C (-40°F
to 140°F)
Ordering Information
Model Number
Description
TDR-1150
Portable Computer Based, Digital
Cable radar (TDR) Color LCD, ARC Reflection, Low Voltage
Direct and Serial Port.
TDR-1150-RTRFT
Retrofit Kit upgrade CDI and
Hipotronics First Response with New TDR 1150. Includes: 1150,
all necessary cable connections, CFFR and charging circuit
modifications, instruction modification book.
Power Supply
100V to 240 Volts AC, 50/60Hz or 12
volts DC
1150-PS Power Supply
100V to 240 Volts AC, 50/60Hz input