Input
Voltage |
110 - 230
Volts 50/60Hz (400 VA) |
|
Output
Voltage
|
Sinusoidal:
0 - 33 kV peak, Symmetrical
DC±: 0 - 30 kV
Accuracy ±1% |
|
Output
Current
|
0 - 15 mA
(Resolution 1µA)
Accuracy ±1% |
|
Resistance Range |
0.1 MΩ
to 5GΩ |
|
Output
Frequency |
0.02 .....
0.1Hz in steps of 0.01Hz (default 0.1Hz) |
|
Output
Load
|
0.5µF @ 0.1
Hz @ 23kV RMS (Approx 5000 ft of cable)*
1.0µF @ 0.05 Hz @ 23kV RMS (Approx 10,000 ft of cable)*
2.5µF @ 0.02 Hz @ 23kV RMS (Approx 25,000 ft of cable)*
5.0µF @ Reduced Voltages and/or Frequencies |
|
Output
Modes
|
AC Hipot
(VLF) Symmetrical and load independent across full range
DC Hipot (plus or negative polarity)
Burn/Fault Condition or Fault Trip Mode
Jacket/Sheath Testing |
|
Memory |
50 Test
Records Stored in non-volatile built in memory |
|
Metering
|
Voltage and
Current (True RMS and/or peak)
Capacitance, Resistance, Time< Flashover Voltage |
|
Duty |
Continuous |
|
HV Cable
|
15 ft (4.5
meters) with Alligator clamps on end (other options available
on request) |
|
Weight |
44 lbs (20
kg) |
|
Computer
Interface |
RS-232
connection (software included) |
|
Dimensions
|
17" (L) x
14" (W) x 10" (H)
(430mm x 360mm x 250mm) |
|
Note:
*Based on a typical cable: 100pF/ft (330pF/m) |
| |
|
| |
|
|
Part
Number |
Description |
|
700 004 |
HV Test
Lead with Quick Coupling MC Connector (15ft/4.5m) |
|
700 002
|
Auxiliary
AC Power Pack with integrated charger to independently
power up instrument. Direct Mechanical Coupling to HVA30 test
instrument. Capacity 21 Ahrs. Weighs 30 lb/14kg. |
|
700 005 |
Transport
Case for HVA30 including compartment for Test
Leads/Hook-up cables. |