Macey's Electrical Logo

 

HV Diagnostics logo

HVA 60 High Voltage Universal
 Test System

HVA 60 Test System Specifications/Options

You are here:  HVA 60 Test System Specifications         
Navigation:  High Voltage Tester Index > HV Diagnostics Equipment Index >
   HVA 60 Features > HVA 60 Functionality > HVA 60 Specifications/options >
 

Input Voltage

88 to 264 Volts 50/60Hz (single-phase)

Output Voltage

 

Sinusoidal: 0 - 60 kV peak
DC±: 0 - 60 kV
Accuracy ±1%

Output Current
 

0 - 50 mA (Resolution 1µA)
Accuracy ±1%

Resistance Range

0.1 MΩ  to 20GΩ

Output Frequency

0.02 ..... 0.1Hz in steps of 0.01Hz

Output Load




 

1.0μF at 0.1Hz at 43kV rms (approx 3km of cable)*
2.0μF at 0.05Hz at 43kV rms (approx 6km of cable)*
5.0μF at 0.02Hz at 43kV rms (approx 15km of cable)*
50μF at reduced voltage and/or frequency

* based on a cable capacitance 330pF/metre

Output Modes


 

AC Hipot (VLF) Symmetrical and load independent across full range
DC positive and negative polarity
Burn/Fault Condition or Fault Trip Mode
Jacket/Sheath Testing

Memory

Up to 50 test records stored in non-volatile built in memory

Metering
 

Output Voltage and Current (true rms and peak)
Capacitance, Resistance, Time, Flashover Voltage

Weight

132 lbs (59.8 kg)

Computer Interface

RS-232 connection (software included)

Dimensions
 

18" (L) x 14" (W) x 20" (H)
(450mm x 350mm x 510mm)

Accessories Supplied

Mains cable, HV output cable, earth cable, RS232 cable, Operating manual

Standards


 

Shock: IEC68-2-27 (15g/11ms half sinus)
Vibration: IEC68-2-6 (10…..150Hz : 2g
EMC: IEC6100-4-2, IEC6100-4-4, EN55011
Safety: EN60950, EN50191,EN61010-1

Temperature

 

Storage: -25º C to +70ºC
Operating: -5ºC to +45ºC
Auto shut down will occur when the internal temperature of the HVA exceeds +65ºC

Safety




 

Short circuit protection
Display indicates all important function and messages
Emergency OFF and operator lockout key
Automatic discharge and earthing of load
Zero output voltage interlock
Zero voltage switching

   

 

 

Options

 

Part Number

Description

700 605

Transport case housing the HVA60 together with all required cables

700 010

Vacuum circuit breaker testing feature upgrade

 

NOTE: Due to Company’s continuous development program the information detailed in this document may change without previous notification

Accles & Shelvoke| Aqua-Tronics | Arbiter Systems | Clare Instruments | Haefely | Hipotronics | HV Diagnostics | Megger | Tettex | T & R Equipment  
Home Page | High Current | High Voltage | Cable Fault | Oil Test | Transformer | Insulation 

 
Macey's Electrical Pty Ltd
ABN 17 344 601 468
Unit 1, 49 Gavenlock Road,  Tuggerah,  Sydney  Australia  2259

 

Phone: 61 2 4353 4644 

Mobile: 0412 678 925

Fax: 61 2 4353 4424

mailto:sales@maceyselectrical.com.au
 

Copyright: 1978 to 2007                                                   Last update: Friday, 03 October 2008