 Test System

HVA 90 Test System Features

You are here:  HVA 90 High Voltage Tester Specifications         
Navigation:  High Voltage Tester Index > HV Diagnostics Equipment Index
   HVA 90 Features > HVA90 Specifications > HVA90 Brochure (PDF) >
   

Input Voltage

210-265 Volts 50Hz

Output Voltage



 

Sinusoidal: 0 - 90 kV peak, Symmetrical, 64kV rms
DC±: 0 - 90 kV
Squarewave: 90kV
Accuracy ±1%
Resolution 0.1kV

Output Current
 

0 - 40 mA (Resolution 1µA)
Accuracy ±1%

Resistance Range

0.1 MΩ  to 5GΩ

Output Frequency

0.01 ..... 0.1Hz in steps of 0.01Hz (default 0.1Hz) - auto frequency selection

Output Load




 

1.0μF at 0.1Hz at 64kV rms (approx 3,300m/11,000ft of cable)*
1.2μF at 0.1Hz at 57kV rms (approx 3,600m/12,000ft of cable)*
10μF at 0.01Hz at 64kV rms (approx 33,000m/100,000ft of cable)*
10μF Maximum Capacitance

* based on a typical cable: capacitance 100pF/ft or 300pF/m

Output Modes


 

AC (VLF) Symmetrical and load independent across full range
DC positive and negative polarity
Burn/Fault Condition or Fault Trip Mode
Jacket/Sheath Testing

Memory

Up to 50 test records stored in non-volatile built in memory

Metering
 

Output Voltage and Current (true rms and peak)
Capacitance, Resistance, Time, Flashover Voltage

Duty

Continuous! No thermal limitation for operating time.

HV Cable

7.5m with end clamps (other options available on request)

Weight

132 lbs (59.8 kg)

Computer Interface

RS-232 connection (software included)

Temperature

Storage -25°C to +70°C, Operating -5°C to +45°C

Weight

280 lbs (127 kg)

Dimensions
 

25.6" (L) x 17.5" (W) x 24" (H)
(650mm x 445mm x 610mm) - also as 19" version available

Accessories Supplied

Mains cable, HV output cable, earth cable, RS232 cable, Operating manual

Standards


 

Shock: IEC68-2-27 (15g/11ms half sinus)
Vibration: IEC68-2-6 (10…..150Hz : 2g
EMC: IEC6100-4-2, IEC6100-4-4, EN55011
Safety: EN60950, EN50191,EN61010-1

Temperature

 

Storage: -25º C to +70ºC
Operating: -5ºC to +45ºC
Auto shut down will occur when the internal temperature of the HVA exceeds +65ºC

Safety




 

Short circuit protection
Display indicates all important function and messages
Emergency OFF and operator lockout key
Automatic discharge and earthing of load
Zero output voltage interlock
Zero voltage switching

   

Ordering Info

 

Part No: SH 0209

Standard HVA90

Part No: SH0223

HVA90 as 19" version

 

 

 

 

Options

 

Part Number

Description

SH0206

TD60 Tan Delta Accessory (option)

SH0222

PD90 Partial Discharge Accessory (option)

VKR 0004

Rugged Transport Case (option)

 

NOTE: Due to Company’s continuous development program the information detailed in this document may change without previous notification

 

Accles & Shelvoke| Aqua-Tronics | Arbiter Systems | Clare Instruments | Haefely | Hipotronics | HV Diagnostics | Megger | Tettex | T & R Equipment  
Home Page | High Current | High Voltage | Cable Fault | Oil Test | Transformer | Insulation 

 
Macey's Electrical Pty Ltd
ABN 17 344 601 468
Unit 1, 49 Gavenlock Road,  Tuggerah,  Sydney  Australia  2259

 

Phone: 61 2 4353 4644 

Mobile: 0412 678 925

Fax: 61 2 4353 4424

mailto:sales@maceyselectrical.com.au
 

Copyright: 1978 to 2007                                                   Last update: Saturday, 14 March 2009