70kV 120kV and 160kV High Voltage DC
                      Dielectric Test Sets - Specifications

You are here:

70kV-120kV-160kV HV DC Dielectric Tester Specifications

Navigation:

High Voltage Tester Index > Megger Product Index >
  70-120-160kV Hipot Tester Features > 70-120-160kV Models/Options/Accessories
 
MODEL CAPABILITIES/APPLICATIONS
Following are the acceptance and maintenance testing
capabilities of each of the dc dielectric test sets.
Maintenance testing on 28kV class cable.
 

70-kV DC Dielectric
Test Set

120-kV DC Dielectric
Test Set

160-kV DC Dielectric
Test Set

  • Acceptance testing on 15kV class cable.
  • Maintenance testing on 28kV class cable.
  • Acceptance testing on 35kV class cable.
  • maintenance testing on 46kV class cable.
  • Acceptance testing on 46kV class cable.
  • Maintenance testing on 115kV class cable.
Input Power
Nominal 120VAC 50/60Hz
For 220/240VAC 50/60Hz operation, add -47 to Cat. no.

Please note that specifications for the -47 models differ as follows:

Output Current (-47 models)
120kV Models: 5mA for 5 minutes; 2mA continuous
160kV Models: 5mA for 5 minutes; 1.5mA continuous

When using external 240/120-volt step-down voltage transformers, the ratings may be used as given for 120 volt input.

Weight: add approx 2lb (1kg) for -47 control unit.

Ammeter (Digital Models)
Ranges

0 to 19.9µA, 0 to 199µA, 0 to 1.99mA, 0 to 5mA

Resolution

To 0.1µA on lowest range

Accuracy

±2% of reading + 1 digit

 

Ammeter (Analog Models)
Ranges

0 to 5µA, 0 to 50µA, 0 to 500mA, 0 to 5mA

Resolution

To 0.1µA on lowest range

Accuracy

±2% of full scale range

 

Voltmeter (Digital Models)
Resolution

To 100Volts over entire range

Accuracy

±(2% of reading + 100 volts)

 

Voltmeter
 (Analog Models)
35kV to 70kV
 
60kV to 120kV
 
80kV to 160kV
 
Resolution 2.5% full scale 1.6% full scale 2.5% full scale
Accuracy ±2% of full scale range ±2% of full scale range ±2% of full scale range

 

Temperature Range
Operating Temperature

-30°C to +55°C (-20°F to +130°F)

Storage Temperature

-40°C to +65°C (-40°F to +150°F)

 

Relative Humidity
Operating

0 to 90% non-condensing

Storage

0 to 95% non-condensing

 

Additional Specifications

Model Test Voltage* Max. Power System
Voltage (phase-to-phase)
Output Current
(120VAC Input)
Display Cat. No.
70kV 0 to 70kVDC 15kVAC 5mA for 30 min Digital 220070
3.5mA continuous Analog 220072
120kV 0 to 120kVDc 35kVAC 5mA for 20 min Digital 220123
2.5mA continuous Analog 220124
160kV 0 to 160kVDC 69kVAC 5mA for 20 min Digital 220163
2mA continuous Analog 220164
Note: *Negative polarity with respect to ground

 

Dimensions 70-kV Models 120-kV Models 160-kV Models
Control Unit

 
20" (H) x 12" (W) x 12.5" (D) 20" (H) x 12" (W) x 12.5" (D) 20" (H) x 12" (W) x 12.5" (D)
510mm (H) x 305mm (W) x 318mm (D) 510mm (H) x 305mm (W) x 318mm (D) 510mm (H) x 305mm (W) x 318mm (D)
High voltage Unit

 
20" (H) x 12" (W) x 12" (D) 29" (H) x 12" (W) x 12" (D) 39" (H) x 12" (W) x 12" (D)
510mm (H) x 305mm (W) x 305mm (D) 740mm (H) x 305mm (W) x 305mm (D) 1000mm (H) x 305mm (W) x 305mm (D)

 

Ripple
  Less than 2% on capacitive samples at continuous rated output

 

Weight 70-kV Models 120-kV Models 160-kV Models
Control Unit 23lb (10.5kg) 23lb (10.5kg) 23lb (10.5kg)
High Voltage Unit 44lb (20kg) 65lb (30kg) 73lb (33kg)
Cables (incl. carrying bag) 7lb (3kg) 9lb (4kg) 9lb (4kg)
 
Click to View Models/Options/accessories


 

Accles & Shelvoke| Aqua-Tronics | Arbiter Systems | Clare Instruments | Haefely | Hipotronics | HV Diagnostics | Megger | Tettex | T & R Equipment  
Home Page | High Current | High Voltage | Cable Fault | Oil Test | Transformer | Insulation 

 
Macey's Electrical Pty Ltd
ABN 17 344 601 468
Unit 1, 49 Gavenlock Road,  Tuggerah,  Sydney  Australia  2259

 

Phone: 61 2 4353 4644 

Mobile: 0412 678 925

Fax: 61 2 4353 4424

mailto:sales@maceyselectrical.com.au
 

Copyright: 1978 to 2007                                                   Last update: Friday, 03 October 2008