| Resistance range |
Test frequency |
| |
0.01 to 2000 autoranging |
|
128 Hz |
| Accuracy |
Test voltage |
| |
2% ±3 digits (digital models) |
|
25 V or 50 V, user selectable
(factory setting
50 V) |
| |
2.5% of scale length (analog
model) |
|
|
| Earth voltage
range |
Test current |
| |
0 – 100 V |
|
450 micro-amps at 25 V or 50 V
(selectable),
4.5mA at 25 V |
| Earth voltage
accuracy |
Noise
rejection |
| |
2% ±2 V |
|
40V pk to pk |
| 2-wire test |
Noise check |
| |
Yes, all models |
|
Automatic (by selector switch
DET3TA) |
| 3-wire test |
C spike check |
| |
Yes, all models |
|
Automatic (by pushbutton
DET3TA) |
| 4-wire test |
P spike check |
| |
DET4TD |
|
Automatic (by pushbutton
DET3TA) |
| ART (Attached
Rod Technique) |
Maximum current
loop resistance |
| |
with current measuring clamp
(DET3TC) |
|
100 k-ohms, 5 k-ohms for
0.01 ohm resolution for readings below 19 ohms |
| Ground current
range |
Maximum voltage
probe resistance |
| |
(with current measuring clamp)
1 mA to 19.9 A (DET3TC) |
|
100 k-ohms, 5 k-ohms for
0.01 ohm resolution for readings below 19 ohms |
| Display |
Battery type |
| |
LCD (moving coil meter for
analog model) |
|
8 ea. 1.5 V AA cells |
| Safety |
Battery life |
| |
EN61010-1 CAT IV 100 V |
|
3 hours, 700 consecutive tests |
| Terminals |
Dimensions |
| |
4 mm plug type (test leads) |
|
8" x 5.7" x 3.2" (203mm x 148mm x 78 mm) |
| Ingress protection |
Weight |
| |
IP54 |
|
2.2 lb (1 kg) |
| EMC |
Operating temperature range |
| |
Meets the requirements of EN61326-1:1998 for use in heavy
industrial areas |
|
-5º to +131º F (-15º to +55º C);
DET3TA: -4º to +122º F (-20º to +50º C) |
| Humidity |
Storage temperature range |
| |
95% RH non-condensing at 104º F (40º C) |
|
-40º to +158º F (-40º to +70º C) |