Specifications for both Models |
|
Guard |
2% error guarding 500kΩ
leakage with 100MΩ load |
|
Capacitance Measurement
|
10nF to 50µF (dependant on measurement
voltage) |
|
Capacitance Measurement |
±5% ±5nF |
|
Accuracy (23°C) |
|
|
Voltage Output Accuracy |
+4% ±10 V of nominal test voltage at 1 GΩ
load ±25V for test voltages less |
|
(0°C to 30°C) |
500 Volts |
|
Current Measurement Range |
0.01 nA to 5mA |
|
Current Measurement |
±5% ±0.2 nA at all voltages |
|
Accuracy (23°C) |
|
|
Display |
Analog/digital 3 digits |
|
Interference Rejection |
2mA rms @ 200 volts and above |
|
Timer Range |
Up to 99 minutes and 59 seconds from start
of test |
|
Memory Capacity |
32 kB |
Test Regimes
|
- Auto Insulation Resistance (IR).
- Polarization Index (PI).
- Dielectric Absorption Ratio (DAR).
- Step Voltage (SV).
- Dielectric Discharge (DD).
|
|
Interface |
RS-232 and USB |
|
Data Store |
Voltage, test time, leakage current,
resistance, PI, DAR, DD, Capacitance |
| |
and time constant |
|
Real Time Output |
Serial, once per second of test voltage,
current and resistance |
|
Environmental Operating
|
-10°C to 65°C |
|
Temperature |
|
|
Storage Temperature |
-25°C to 65°C |
|
Ingress Protection (lid Closed) |
IP65 |
|
Humidity |
90% RH non-condensing at 40°C |
|
Safety |
Meets the requirements of EN 61010-1: 2001
CAT III 300V |
|
EMC |
Meets the requirements of EN 61326-1: 1998
for use in heavy industrial areas |
|
Dimensions |
305mm x 194mm x 360mm (12.7" x 6" x 14.2") |
|
Weight |
7.1 kg (16lb) approx |