Specifications
Range Model MIT520 Model MIT1020
Voltage Input Range 95V to 240V ±10% 50/60Hz 95V to 240V ±10% 50/60Hz
Battery Life 6 hours continuous testing at 5kV 4 hours continuous testing at 10kV
Test Voltages 50V to 1kV in 10V steps 50V to 1kV in 10V steps
  1kV to 5kV in 25V steps 1kV to 10kV in 25V steps
Accuracy (23°C) ±5% to 1 TΩ ±5% to 1 TΩ
  ±20% to 10 TΩ ±20% to 20 TΩ
Display Range    

Digital Display:

10kΩ to 15 TΩ 10kΩ to 35 TΩ

Analog Display:

100kΩ to 1 TΩ to 1 TΩ
Short Circuit/Charge Current 5mA 5mA
Capacitor Charge Time 1.5 seconds/µF at 5mA to 10kV 3 seconds/µF at 5mA to 10kV
Capacitor Discharge Time 120ms/µF to discharge from 250ms/µF to discharge from
  5000 Volts to 50 Volts 10,000 Volts to 50 Volts
 
 
 
 
Specifications for both Models
Guard 2% error guarding 500kΩ leakage with 100MΩ load
Capacitance Measurement 10nF to 50µF (dependant on measurement voltage)
Capacitance Measurement ±5% ±5nF
Accuracy (23°C)  
Voltage Output Accuracy +4% ±10 V of nominal test voltage at 1 GΩ load ±25V for test voltages less
(0°C to 30°C) 500 Volts
Current Measurement Range 0.01 nA to 5mA
Current Measurement ±5% ±0.2 nA at all voltages
Accuracy (23°C)  
Display Analog/digital 3 digits
Interference Rejection 2mA rms @ 200 volts and above
Timer Range Up to 99 minutes and 59 seconds from start of test
Memory Capacity 32 kB
Test Regimes




 
  • Auto Insulation Resistance (IR).
  • Polarization Index (PI).
  • Dielectric Absorption Ratio (DAR).
  • Step Voltage (SV).
  • Dielectric Discharge (DD).
Interface RS-232 and USB
Data Store Voltage, test time, leakage current, resistance, PI, DAR, DD, Capacitance
  and time constant
Real Time Output Serial, once per second of test voltage, current and resistance
Environmental Operating -10°C to 65°C
Temperature  
Storage Temperature -25°C to 65°C
Ingress Protection (lid Closed) IP65
Humidity 90% RH non-condensing at 40°C
Safety Meets the requirements of EN 61010-1: 2001 CAT III 300V
EMC Meets the requirements of EN 61326-1: 1998 for use in heavy industrial areas
Dimensions 305mm x 194mm x 360mm (12.7" x 6" x 14.2")
Weight 7.1 kg (16lb) approx

 

Accles & Shelvoke| Aqua-Tronics | Arbiter Systems | Clare Instruments | Haefely | Hipotronics | HV Diagnostics | Megger | Tettex | T & R Equipment  
Home Page | High Current | High Voltage | Cable Fault | Oil Test | Transformer | Insulation 

 
Macey's Electrical Pty Ltd
ABN 17 344 601 468
Unit 1, 49 Gavenlock Road,  Tuggerah,  Sydney  Australia  2259

 

Phone: 61 2 4353 4644 

Mobile: 0412 678 925

Fax: 61 2 4353 4424

mailto:sales@maceyselectrical.com.au
 

Copyright: 1978 to 2007                                                   Last update: Friday, 03 October 2008