Range |
Model MIT510 |
|
Electrical Specifications |
|
|
Voltage Input Range |
85V to 260V 50/60Hz |
|
Battery Life |
8 hours continuous testing at 5kV |
|
Test Voltages |
250V, 500V, 1000V, 2500V, 5000V |
|
Accuracy (23°C) |
±5% to 100 GΩ |
| |
±10% to 15 TΩ |
|
Display Range |
|
|
Digital
Display: |
10kΩ to 15 TΩ |
|
Analog
Display: |
100kΩ
to 1 TΩ |
|
Short Circuit/Charge Current |
3mA |
|
Capacitor Charge Time |
≤5
seconds/µF at 3mA |
|
Capacitor Discharge Time |
≤5
seconds/µF
to discharge from 5000 Volts to 50 Volts |
|
Capacitance measurement |
1nF to 50 μF (measured with test voltage ≥
500 V) |
|
Capacitance measurement accuracy (23°C) |
±5% ±5 nF |
|
Voltage output accuracy (0°C to 30°C) |
±2% ±1 V of nominal test voltage at 100 MΩ
load |
| |
±25 V for test voltages less than 500 V |
|
Current measurement range |
±0.01 nA to ±5 mA |
|
Current measurement accuracy (23°C) |
±5% ±0.2 nA at all voltages |
|
Display |
Analogue/Digital 3 digits |
|
Interference rejection |
1mA rms per kV test voltage, 2 mA rms
maximum |
|
Timer range |
Up to 99 minutes |
|
Test regimes |
Auto IR |
|
Lead set |
Three leads with compact clamp, flexible
silicon insulated |
|
Environmental |
|
|
Operating temperature |
-10°C to 50°C |
|
Storage temperature |
-25°C to 65°C |
|
Ingress protection (lid closed) |
IP54 |
|
Humidity |
90% RH non-condensing at 40°C |