Output
Initiate Circuit
The test set uses a
solid-state output initiating circuit. To increase
reliability and eliminate contact
maintenance, this circuit uses a triac instead of a
contactor to initiate the output.
The initiating
circuit provides momentary and maintained modes to control
output duration. The momentary mode is used whenever the
output is to be on for a short duration, such as when
performing instantaneous trip tests, or to avoid damage or
overheating of the device under test while setting the test
current. In the maintained mode, the output remains
energized until manually turned off or, when performing
timing tests, until the device under test operates — which
both stops the timer and de-energizes the output.
Instrumentation
|
Ammeter |
|
|
Operating Modes
(switch-selectable) |
Memory
Normal |
|
Display
|
3.5 Digit, extra-bright LED
display with 0.3 inch (7.62mm) numerals. |
|
|
Ranges (switch-selectable) |
0 to 1.999/19.99/199.9/750A |
|
|
Continuous Accuracy (overall
ammeter system) |
±1% of reading, ±1 digit on
three high ranges
|
|
|
Regulating |
±1% of range, ±1 digit on low
range |
|
| |
|
|
| |
|
|
|
Timer |
|
Display
|
5-digit, extra-bright, LED
display with 0.3 inch (7.62mm) numerals. |
|
Ranges (switch-selected)
|
0 to 99.999 s
0 to 999.99 s
0 to 99999 cycles |
|
|
Accuracy |
±0.005% of reading, ±1 digit |
|
Timer Control Circuit
This circuit automatically starts the timer when
the output is energized and automatically stops the timer
and de-energizes the output when the device under test
operates. This circuit accommodates the following test
conditions by simple switch selection of the appropriate
mode:
Current Actuated
Used to test a device that has no auxiliary contacts to
monitor, such as a single-pole circuit breaker. The timer
stops when the output current is interrupted.
Normally Closed
Used to test a device with normally closed contacts. The
timer stops and the output is de-energized when the
contacts open.
Normally Open
Used to test a device with normally open contacts. The
timer stops and the output is de-energized when the
contacts close.
Enclosure
The test set is housed in a high strength, molded,
suitcase-type enclosure with carrying handle and removable
cover. Storage space is provided for test leads.
Dimensions
9.9" (H) x 14" (W) x 11" (D)
25cm (H) x 35cm (W) x 28cm (D)
Weight
33 lb (15 kg) |