Specifications |
|
Current Output |
0 to 100 A at 0 to 24 V a.c. |
| |
0 to 30 A at 0 to 80 V a.c. |
| |
0 to 10 A at 0 to 240 V a.c. |
| |
Maximum currents are short-term
values. (Each of these outputs has a separate terminal
referred to one common terminal.) |
|
Duty Cycle |
For Maximum Short-Term Current 1 min
'ON' circuit and 15 min 'OFF' circuit. |
| |
For Half-Maximum Short-Term Current 5
min 'ON' circuit and 15 min 'OFF' circuit. |
| |
For Quarter-Maximum Short-Term. |
|
Current |
Continuous operation |
|
Voltage Output |
0 to 240 V d.c., 1 A (This is not a
floating output.) |
| |
0 to 120 V a.c., 0,5 A (This output is
fully floating and under normal loading is in phase with the
current to within 10%.) |
| |
Each of these outputs has a separate
pair of terminals. |
| |
|
|
Displays |
|
Current/Voltage |
3.5-digit LED |
Counter |
5-digit LED, crystal controlled
(3,2768 MHz) 9 minutes 59,99 seconds with overrange
indication. |
|
Dimensions/Weight |
|
Dimensions |
368mm (H) x 500mm (W) x 310mm (D)
((14" (H) x 19" (W) x 12" (D) approx) |
|
Weight |
41 kg (90 lb approx) |
| |
|
| |
|
|
SF30 Filter Unit
Specifications |
|
Ranges
All outputs are relative to a
common terminal. |
0 to 1 A 1 to 2 A 2 to 5 A 5 to 10 A 10 to 30 A |
Dimensions |
490mm (H) x 165mm (W) x 270mm (D) mm (19" (H) x 6" (W) x 10" (D) approx) |
|
Weight |
13 kg (30 lb approx) |
| |
|
|
General Specifications |
|
Supply Voltage |
220/240 V ±10%, 50/60 Hz |
Safety |
The test set will, in general,
meet the requirements of the BS 4743 (1979), IEC 348 (1978),
BS 5458 (1977)and IEC 414 (1973) specifications. |
Temperature Range |
Operating: 0 to +40°C (32 to
104°F) Storage: -20 to +70°C (-4 to 158°F) |
| |
|
|
Instrument Protection |
|
Input Circuits
|
1 amp, 20mm x 5 mm HBC (T) fuse to IEC
127 standard sheet III |
|
10 amp, 32mm x 6 mm HBC fuse |
|
Output Circuits
|
240 V
d.c.: 1 amp, 20mm x 5 mm HBC fuse |
|
120 V
a.c.: 0,5 amp, 20mm x 5 mm HBC fuse |
|
Thermal switch operates when current
transformer temperature >80°C (176°F). |
Thermo-magnetic contact operates
when main output control current >7,5 A. |
| |
|
| Ordering
Information |
| |
|
|
Model |
Description |
|
SCITS100 |
Secondary Current Injection Test Set |
| |
|
| |
|
| Included
Accessories |
| |
|
|
Catalog Number |
Description |
|
5310-245 |
Cover, black ABS plastic |
|
6121-181 |
One set spare fuses |
|
6171-148 |
Operation instruction book |
|
6220-302 |
Lead storage bag, cotton reinforced
PVC. |
|
6231-216 |
Remote counter control switch, (2
meter lead) |
| |
|
| |
|
| Optional
Accessories |
| |
|
|
Catalog Number |
Description |
|
6220-303 |
One set 100 amp leads (LEADS/100( |
|
6320-224 |
Transportation trolley |
|
6410-223 |
SF30 Filter Unit, 30 amp |