|
Transformer
Turns Ratio
Transformer Turns Ratio is the ratio of the number of turns in the
high voltage winding to that in the low voltage
winding. A Transformer Turns Ratio Test Set such as the Three-phase
Automatic TTR can directly measure the ratio of most types of
transformers. Transformer ratio can change due to several factors,
including physical damage from faults, deteriorated insulation,
contamination and shipping damage. If a transformer ratio changes
more than 0.5 percent from the rated voltage ratio, it may not
operate reliably. To measure small ratio changes such as this, the
accuracy of a Biddle TTR is needed.
Excitation
Current
The exciting current is the current that maintains the magnetic flux
excitation in the core of a transformer.
A Transformer Turns Ratio Test Set such as the Three-phase Automatic
TTR is capable of measuring exciting current because they apply
voltage to one of the transformers windings. An accurate measurement
of exciting current can provide information about the condition of a
transformer’s core. Unwanted circulating currents or unintentional
grounds can affect the exciting current and indicate a problem.
Phase Angle
Deviation
The phase angle deviation is the relationship between the voltage
signal applied to the high voltage winding and the voltage signal
extracted from the low voltage winding.
The phase deviation between
the high and low side of a transformer is generally very small. If
there is deterioration or damage in the transformer core, however,
the phase deviation can change significantly. The Three-phase TTR
can measure this phase relationship with the resolution necessary to
detect a problem.
|