Macey's Electrical Logo

Megger logo

Transformer Testing Equipment

Transformer Winding Resistance/Tap-Changer

 
Three features combine to make this instrument unique: dual measurement, load tap-changer testing and safety shutdown.

 

 

Features
  • Direct digital reading.
  • Built-in discharge circuitry.
  • Two independent measuring channels.
  • Tests operation of on-load tap-changers.

Description
The Transformer Ohmmeter is a line-operated, field portable instrument designed specifically to measure the dc resistance of all types of magnetic windings safely and accurately.

Its predominant use is the measurement of the dc resistance of all types of transformer windings within the defined ranges of current and resistance. It can also test rotating machine windings and perform low-current resistance measurements on connections, contacts and control circuits.

 
Three features combine to make this instrument unique: dual measurement, load tap-changer testing and safety
shutdown. The dual set of potential inputs measure the resistance of the primary and secondary windings of a single- or three-phase transformer simultaneously. The dual reading characteristic will speed up the measurement when it is used to test windings on delta-delta connected windings on three-phase transformers.

Due to circulating currents induced when the test current is applied to the primary winding, this type of measurement is countered by the same current on the secondary winding. This action attenuates the circulating current and the reading time is improved tenfold.

The Transformer Ohmmeter is extremely useful when testing the windings and contact resistance on tap changers with make-before-break contacts and voltage regulators.

The internal shutdown circuit will be triggered by a voltage kickback of a few microseconds if the tap-changer
contacts are opened when the tap-changer circuit is operated through all of the tap positions. This action will check for pitted or misaligned contacts as the instrument will shut down if either condition occurs.

Users are protected by the shutdown circuit safety feature: any inadvertent disconnection of a test lead or loss of power to the instrument will safely discharge the energy stored in the test sample.
 

Applications
The Transformer Ohmmeter is used:
  • To verify factory test readings.
  • As part of a regular maintenance program.
  • To help locate the presence of defects in transformers, such as loose connections.
  • To check the make-before-break operation of on-load tap-changers.

A regular maintenance program that includes winding resistance measurements is the most effective way to use
this instrument. Once a benchmark is established, subsequent test results can be compared to determine if changes are occurring in the transformers, instrument transformers and associated control wiring, voltage regulators, motors, generators, breaker contacts, all types of connections (bolted, soldered, crimped, etc.).

Tap-changers are mechanical devices and the most vulnerable part of a transformer. Tap-changers result in more failures and outages than any other component and so require frequent testing and attention to ensure proper, reliable operation.

The Transformer Ohmmeter can be used to check the make-before-break operation of on-load tap-changers and also to measure the contact resistance of each tap position.

Schematic comparison of one-and-two winding measurements.

Schematic comparison of one-and-two winding measurements


 

Accles & Shelvoke| Aqua-Tronics | Arbiter Systems | Clare Instruments | Haefely | Hipotronics | HV Diagnostics | Megger | Tettex | T & R Equipment  
Home Page | High Current | High Voltage | Cable Fault | Oil Test | Transformer | Insulation 

 
Macey's Electrical Pty Ltd
ABN 17 344 601 468
Unit 1, 49 Gavenlock Road,  Tuggerah,  Sydney  Australia  2259

 

Phone: 61 2 4353 4644 

Mobile: 0412 678 925

Fax: 61 2 4353 4424

mailto:sales@maceyselectrical.com.au
 

Copyright: 1978 to 2007                                                   Last update: Friday, 03 October 2008