Macey's Electrical Logo

Megger logo

Transformer Testing Equipment

TTR-100 Single-Phase Hand Held TTR

You are here:

 TTR100 Single Phase Hand-held TTR Specifications
Navigation:  Transformer Testing Equipment Index > Megger Product Index >
   TTR100 Applications > Specifications > Accessories > Ordering Details
 

Specifications

Type of Power Rechargeable NIMH battery pack, 3.6 V dc, 3800 mAh
Battery Life 15 hours of field operation
Charger Input Voltage
 
100-250 V ac, 50/60 Hz ±2 Hz Unit can be operated while
charging. Charging time is approximately three hours.
Optional Charger Source
 
Optional inverter 12 V dc to 115 V ac for powering a charger from
vehicle battery
Excitation Voltage


 
8 V rms for testing distribution or power transformers, and PTs;
1.5 V ac RMS, or 8 V ac RMS for testing CTs.
The excitation voltage is switched automatically if excitation
current exceeds a preset value.
Test Frequency 55 Hz internally generated providing a universal 50/60 Hz test set
Excitation Current Range 0 to 100 mA, 4-digit resolution
Turns Ratio Range 0.8 to 20,000; 5-digit resolution
Phase Deviation Range
 
±90º, 1 decimal point for the minutes display, 2 decimal points for
the degree display, or for the centiradians display
Winding Resistance Range 0 to 2000 Ω, 4 digit resolution
Transformer Vector Group 1PH0 or 1PH6
Transformer Polarity Additive or Subtractive
Current (rms) Accuracy ±(2% of reading + 1 digit)
Phase Deviation Accuracy ±3 minutes
Turns Ratio Accuracy

 
±0.1% (0.8 to 2000)
±0.15% (2001 to 4000)
±0.25% (4001 to 20.000)
Winding Resistance Accuracy

 
±(10% of reading + 1 digit) for 10 Ω to 2000 Ω range
±(10% ±1 mΩ) for 10 mΩ to 9.99 Ω range
±(10% ±0.5 mΩ) for 0.1 mΩ to 9.99 mΩ range
PC/Printer Interface RS232C port, 9-pin, 57.6 Kbaud (19.2 Kbaud for the printer)
Display Full Graphics
 
LCD module, wide temperature range, 128 x 64 dots (21
characters by 8 lines)
Test Result Storage





 
Internal, nonvolatile memory for storing up to 200 sets of single-phase measured and calculated ratio, exciting current, phase, ratio
error, winding resistance, polarity, vector group, plus header
information (company, substation, transformer manufacturer,
transformer rating, instrument serial number, temperature, relative
humidity, and operator name) In addition, up to 100 user-defined transformer settings can be stored.
Computer Software
 
Included software for downloading of data to a PC, data storage
to database and report printout.
Test Leads
 
Supplied with one complete set of single-phase leads, 6 ft (1.8 m)
in length
Transformer Winding Phase Relationship

 
ANSI C57.12.70-1978
CEI/IEC 76-1:1993 and Publication 616:1978
AS-2374, Part 4-1982 (Australian Standard)
Safety/EMC/Vibration Meets the requirements of IEC-1010-1, CE and ASTM D999.75
Temperature Range
 
Operating: -4º F to 131º F (-20º C to 55º C)
Storage: -58º F to 140º F (-50º C to 60º C)
Relative Humidity
 
Operating: 0 to 90% non-condensing
Storage: 0 to 95% non-condensing
Protective Devices
 
High voltage side shorting relays, transient voltage suppressors
and gas surge voltage protectors
Measuring Time 8 to 20 seconds for a single-phase distribution transformer
Measurement Method ANSI/IEEE C57.12.90
Dimensions
 
9.5" (H) x 4.5" (W) x 1.875" (D)
(241mm (H) x 115mm (W) x 48mm (D)
Weight Approx. 3.3 lbs (1.5 kg), instrument only, without leads
Protective Instrument Carrying Case


 
Neoprene case with carrying strap and attachable pouch for
universal charger and 6 ft. (1.8 m) test leads, single-phase
connection (two leads for the H winding and three leads for the
secondary winding with tap).


 

Accles & Shelvoke| Aqua-Tronics | Arbiter Systems | Clare Instruments | Haefely | Hipotronics | HV Diagnostics | Megger | Tettex | T & R Equipment  
Home Page | High Current | High Voltage | Cable Fault | Oil Test | Transformer | Insulation 

 
Macey's Electrical Pty Ltd
ABN 17 344 601 468
Unit 1, 49 Gavenlock Road,  Tuggerah,  Sydney  Australia  2259

 

Phone: 61 2 4353 4644 

Mobile: 0412 678 925

Fax: 61 2 4353 4424

mailto:sales@maceyselectrical.com.au
 

Copyright: 1978 to 2007                                                   Last update: Friday, 03 October 2008