Product Features
The NEW 200ADM-P redefines the manual secondary injection test set. The unit has an auxiliary ac output can also be used as a second current source and ultra-fine current control on the main output using I limit mode. All results can be stored to a USB memory stick for export to a PC. New Product

 

 

 

  • Clear and simple user interface.
  • 0-200A output current.
  • True RMS metering with 1 cycle capture.
  • Variable auxiliary AC voltage/current output
    with phase shift.
  • Auxiliary metering input V, f,Φ, Z, P, S, PF,
    CT ratio, harmonics.
  • Variable auxiliary output 12V-220Vdc.
  • Multi-function auto-ranging timing system.
  • Current limit mode for fine control.
  • Data storage to USB memory key including waveform and harmonics.
  • USB keyboard/printer interface.
  • Automatic mains voltage selection.

Product Description
The unit has a range of outputs allowing injection of currents between 1mA and 200A. Voltages up to 240V are available on the main outputs allowing high impedance current relays to be tested. True RMS metering with single cycle capture is provided. 4 current ranges allow the full scale of the meter and trip level to be set independently of the selected output. Industry standard safety connectors are used throughout for safe, reliable convenience.

The 200ADM-P has a flexible auxiliary ac output that can be used at up to 260V for voltage relays or up to 10A for current relays. The phase and frequency of this output are fully adjustable. This combination of voltage and current allows testing of relays that require two voltages, one voltage and one current or two currents.

An auxiliary metering module is provided that meters ac and dc voltage, current and frequency from the auxiliary outputs or external signals. The module can also take measurements in conjunction with the main current output to meter phase angle, power, impedance, CT ratio and harmonics.

A variable stabilized DC supply with current limit is provided to power the relay under test.

The unit has a comprehensive timing system linked to the outputs allowing trip times, reset times and reclose times to be quickly measured to a high degree of accuracy. The timer includes a current operated mode and can accurately test instantaneous trips.

Two USB host sockets are provided to connect a memory key, keyboard or printer. Results of every test can be stored to the memory key in spreadsheet format for later analysis. The keyboard allows entry of a comment against each result. In addition a graphics file of the waveform may be stored to the memory key. Harmonics analysis results can also be recorded.

The back-lit display on the 200ADM is bright and clear with a wide viewing angle. The results of a test can be seen here as they appear on the display

T-R 200ADM-P Display

200ADM-P Applications
 
IEEE No. Type   IEEE No. Type
21 Distance protection (phase at a time)   67 Direction overcurrent
24 Volts/Hz   67N Directional ground fault
25 Check sync   78 Phase angle
27/59 Under/over voltage   79 Auto recloser
32/P/Q Directional power   81 Under/over frequency
37 Under-current/power   85 Pilot wire relay
40 Field relay   86 Lockout relay
46N Negative sequence over-current relay   87 Differential relay
50/76 Instantaneous over-current   91 Directional voltage relay
50 Ground fault relay   92 Power directional relay
50V Voltage restrained over-current   94 Tripping relay
51 IDMT over-current relay     Voltage regulating relay
55 Power Factor relay     Miniature circuit breakers
59G Neutral voltage displacement     Thermal relays
        CT mag curves
200ADM-P Specifications

200ADM-P Datasheet (PDF)

 

Accles & Shelvoke| Aqua-Tronics | Arbiter Systems | Clare Instruments | Haefely | Hipotronics | HV Diagnostics | Megger | Tettex | T & R Equipment  
Home Page | High Current | High Voltage | Cable Fault | Oil Test | Transformer | Insulation 

 
Macey's Electrical Pty Ltd
ABN 17 344 601 468
Unit 1, 49 Gavenlock Road,  Tuggerah,  Sydney  Australia  2259

 

Phone: 61 2 4353 4644 

Mobile: 0412 678 925

Fax: 61 2 4353 4424

mailto:sales@maceyselectrical.com.au
 

Copyright: 1978 to 2007                                                   Last update: Wednesday, 10 December 2008