Model 200ADM Specifications

Navigation:

High Current Tester Index >  T&R Test Equipment Index >  200ADM Features

 
200ADM Specifications
Main Output
The main output on the unit has four taps, allowing the selection of output voltages up to 240V and output currents up to 200A.
 
Range Continuous 5 minutes 1 minute 6 seconds  
10V 25A 50A 100A 200A*  
35V 10A 20A 30A    
100V 3A 5A 10A    
240V 1A 2A 3A    
240V DC 1A 2A 3A    
The above intermittent on times must be followed by an off time of 15 minutes, and are based on an ambient temperature of 25°C.
Note: *6 second intermittent ratings are only available up to the 50% position of the output control on a 115V supply.

Auxiliary AC and DC Outputs
A switched, isolated auxiliary DC supply is available to power the relay under test. The output is protected by a fuse and electronic trip circuit.

DC stabilized output

 
24V 1.04A  
48V 0.52A  
60V 0.42A  
110V 0.23A  
220V 0.11A  

The auxiliary AC output is isolated, switched, and fuse protected.

Variable AC output 0 to 130Vac 300mA  
 
Metering
The output is metered by a digital true RMS system with a memory ammeter - whenever the timer stops and the output is switched off, the current reading is held on the display.
Range Resolution Trip current Accuracy  
5.000A 0.001A 5.5A ±0.5% rdg+5 digits  
20.00A 0.01A 22A ±0.5% rdg+5 digits  
50.00A 0.01A 55A ±0.5% rdg+5 digits  
200.0A 0.1A 220A ±0.5% rdg+5 digits  

A current trip is automatically set to 110% of full scale of the selected metering range to protect the device under test.

Auxiliary Metering Inputs
An auxiliary metering input is provided which is able to measure RMS and DC voltage or current. In addition the frequency of the external input may be measured, and the phase measured between the main output current and the auxiliary metering input.

Setting Range Resolution Accuracy  
Volts (DC) 270.0V 0.1V ±0.7% rdg+5 digits  
Volts (AC) 270.0V 0.1V ±0.7% rdg+5 digits  
Amps (DC) 5.000A 1mA ±0.7% rdg+5 digits  
Amps (AC) 5.000A 1mA ±0.7% rdg+5 digits  
Phase   0.1° ±3°  
Frequency 20 to 1000Hz 0.1Hz ±0.2% rdg+1 digits  

The current input is protected by a F6.3A fuse.

Timing System

Range 0 to 999.999 seconds
Resolution 1ms
Accuracy
 
0.1% of rdg + 2 digits
(+4 digits operated mode)

The contact circuit has an open circuit voltage of 24Vdc and a short circuit current of 10mA. Each contact circuit will auto-select for normally open or normally closed contacts. A DC voltage of 24-240Vdc may also be used to trigger either timer channel.

The following functions are provided:

Mode Timer Start Timer Stop  
Internal start Press 'ON' Contact 1 or 2  
Single contact Contact 1 Contact 1  
Dual contact Contact 1 Contact 2  
Current operated Current > 10% of range Current < 10% of range  

Pulse mode is used for setting the current level in devices sensitive to heating, and allows current to be injected for 400ms and the current recorded.

The output is automatically switched off at the end of the test to safeguard the relay under test.

RS 232 Communication Port
An RS232 port is provided to allow connection of a printer.

Protection and Safety
The unit is protected by electronic over current and duty cycle trips on the outputs, thermal monitoring on the power components, and fuses on the input and regulator. The auxiliary AC output is fuse protected, and the stabilized DC output is protected by an electronic trip and fuse. An earth terminal is provided for connection to a local earth.

The unit is designed to comply with BSEN61010, and is CE marked.
 

Supply Requirements (200ADM)

Supply Requirements

 
115V±10%, 50/60Hz 1ph 2300VA max  
230V±10%, 50/60Hz 1ph 2300VA max  

The correct range is automatically selected by the set.

Temperature Range
Storage -20°C to 60°C,   Operating 0°C to 45°C

Lead Set Specifications
The 200ADM is supplied with a lead set including the following items:
  • 2 each 5m 25mm2 200A leads terminated in M10 ring crimps.
  • 2 each 5m 2.5mm2 25A leads terminated in 4mm plugs.
  • 2 each 5m 2 core auxiliary leads terminated in 4mm plugs.

The lead set is supplied in a plastic carrying case.

Dimensions
380mm (H) x 314mm (W) x 221mm (D)

Weight
20.7kg (Including handle and corner protectors)

Accessories supplied with unit
Operating manual, output lead set, mains lead, spare fuse set.

Optional Accessories
Filter unit, Printer

 

Accles & Shelvoke| Aqua-Tronics | Arbiter Systems | Clare Instruments | Haefely | Hipotronics | HV Diagnostics | Megger | Tettex | T & R Equipment  
Home Page | High Current | High Voltage | Cable Fault | Oil Test | Transformer | Insulation 

 
Macey's Electrical Pty Ltd
ABN 17 344 601 468
Unit 1, 49 Gavenlock Road,  Tuggerah,  Sydney  Australia  2259

 

Phone: 61 2 4353 4644 

Mobile: 0412 678 925

Fax: 61 2 4353 4424

mailto:sales@maceyselectrical.com.au
 

Copyright: 1978 to 2007                                                   Last update: Friday, 03 October 2008