T & R Test Equipment Models KV50-200 and KV100-100 High Voltage Testers.
  • 0 to 100kV (KV100-100) output voltage.
    or 0 to 50kV (KV50-200) output voltage.
  • 10kVA output capability.
  • Low partial discharge option available (LD suffix units).
  • Key operated supply switch to prevent unauthorized operation.
  • Dual overload protection.
  • Variable electronic trip—10-100% of rated output.
  • Voltage and current metering.
  • External 24Vac interlock circuit.
  • Zero-volt interlock.
  • Visual indication of test piece failure.

 

 

 

Product Description
The KV50-200 and KV100-100 are high power, high voltage ac test systems designed for insulation testing. These systems are equally suited to both development and routine testing of electrical insulation systems and plant. Each unit is available in either a low partial discharge version or without a specified discharge level.

The equipment consists of a control unit and a separate oil filled high voltage transformer, linked by 5 metre supply and control cables. The control unit is fitted with a comprehensive range of facilities for control, metering and protection. Both systems include secondary tap metering as standard to ensure accurate voltage metering. The output voltage and current are displayed on large, linear analogue instruments, and a variable electronic trip is provided, allowing the trip current to be set to 10-110% of rated output.

The high voltage transformer is housed in an oil-filled steel tank fitted with swivel castors for mobility. The units use a low-discharge oil-filled bushing for the HV output. Both the KV50-200 and KV100-100 are equally suited to testing capacitive, resistive or inductive test objects.

Low discharge versions of the units are available as an option (KV50-200LD and KV100-100LD), with maximum discharge levels of 1pC and 3pC respectively. The partial discharge levels on the standard KV50-200 and KV100-100 are not specified.

KV50-200 and KV100-100 Specification

Output
The output of the KV series units is by an oil filled high voltage bushing. The earthy end of the HV winding is connected to earth via the current metering circuit and a removable link. The removable link allows equipment supplied by the user to be connected into the earthy end of the HV winding for Tan-d measurements.

Continuous Ratings

KV50-200

KV100-100

 
Voltage 0 to 50kVA ac 0 to 100kV ac  
Current 100mA 50mA  
Power 5kVA 5kVA  
 
 
Intermittent Ratings (5 minutes ON and 15 minutes OFF)

Intermittent Ratings

KV50-200

KV100-100

 
Voltage 0 to 50kVA ac 0 to 100kV ac  
Current 200mA 100mA  
Power 10kVA 10kVA  


If you require a different output voltage test system, please contact us with your specification and we will quote for a custom design.

Metering
The output voltage is metered using a tap on the  HV winding connected to an average-reading dual scaled analogue instrument.

Metering x0.5 Range x1 Range Accuracy  
KV50-200 0 to 30kV 0 to 60kV ±2% of FS  
KV100-100 0 to 50kV 0 to 100kV ±2% of FS  

Load current is metered in the earthy end of the HV winding connected to an average-reading dual scaled analog instrument.

Load Current Metering mA Meter Accuracy  
KV50-200 0 to 240mA ±2% of FS  
KV100-100 0 to 100mA ±2% of FS  


Control
The output voltage is set by a continuously variable output control with a zero volt interlock - the output may only be switched on with the control in the zero position. The output voltage is switched on and off by illuminated push button switches.

The mains supply switch for the unit is a key operated switch. The key is trapped in the switch in the ‘on’ position.
 

Supply Requirements  
KV50-200 230V±10%, 50/60Hz 1ph 11kVA max  
KV100-100 230V±10%, 50/60Hz 1ph 6kVA max  
 

Partial Discharge
The KV50-200LD and KV100-100LD have a specified low partial discharge level, and are suitable for making partial
discharge measurements in the object under test. The partial discharge level of the standard KV50-200 and KV100-100 is not specified.

Device Maximum PD  
KV50-200 Not specified  
KV100-100 Not specified  
KV50-200LD 1pC  
KV100-100LD 3pC  
 

Protection and Safety
The output of the units are protected by variable electronic trips monitoring the output current, and a fixed overcurrent trip on the primary of the output transformer. The variable trip is adjustable in 10% steps between 10% and 110% of the rated output current.

The input and control supplies are protected by fuses.

The KV50-200 and KV100-100 are designed to meet the requirements of BS EN61010. An earth terminal is provided on the transformer which must be connected to a low impedance local earth.
 

Interlock Circuits
Two interlock circuits are provided on the kV series test systems. A zero voltage interlock is fitted which prevents
the HV output being energized unless the output voltage control is in the zero position. A 24Vac external interlock
circuit is also provided, allowing the fitting of external emergency off buttons and test cage door interlocks.

Temperature Range
Storage -20°C to 60°C,   Operating 0°C to 45°C

Dimensions Weight  
KV50-200 Control Unit 370mm (H) x 480mm (W) x 290mm (D) Weight 37kg  
KV100-100 Control Unit 370mm (H) x 480mm (W) x 290mm (D) Weight 37kg  
KV50-200 Transformer 570mm (H) x 500mm (W) x 1020mm (D) Weight 220kg  
KV100-100 Transformer 730mm (H) x 650mm (W) x 1350mm (D) Weight 390kg  
 

Accessories supplied with Unit
One 5 meter Power interconnecting lead.
Two 5 meter Metering interconnection leads.
Spare fuse set, and Operating manual.

Optional Accessories
Test duration timer.


 

Accles & Shelvoke| Aqua-Tronics | Arbiter Systems | Clare Instruments | Haefely | Hipotronics | HV Diagnostics | Megger | Tettex | T & R Equipment  
Home Page | High Current | High Voltage | Cable Fault | Oil Test | Transformer | Insulation 

 
Macey's Electrical Pty Ltd
ABN 17 344 601 468
Unit 1, 49 Gavenlock Road,  Tuggerah,  Sydney  Australia  2259

 

Phone: 61 2 4353 4644 

Mobile: 0412 678 925

Fax: 61 2 4353 4424

mailto:sales@maceyselectrical.com.au
 

Copyright: 1978 to 2007                                                   Last update: Friday, 03 October 2008