Macey's Electrical Logo

T and R Test Equipment logo

High Current Test System

PCU1 Primary Current Injection System

 

You are here:

Models PCU1-SP and LT Features

Navigation:

High Current Tester Index >  T&R Test Equipment Index > PCU1 Specifications

 
Product Features
The PCU1 series are medium powered primary current injection systems offering output currents up to 5000A. Features (PCU1-LT and PCU1-SP)
  • 5kA maximum output current (higher overload currents for 2s).
  • Multi-function digital timing system.
  • Digital true RMS memory ammeter.
  • Solid state switching.
  • 2000A and 5000A loading units.
  • Three range outputs on loading units.
  • Rugged, compact design.
  • Optional trolley mounting of system.

PCU1-SP Additional Features

  • Secondary injection up to 100A.
  • Direct reading CT ratio and polarity.

Product Description
The PCU1 series are medium powered primary current injection systems offering output currents up to 5000A. The system consists of a separate control unit containing all metering and control functions and a loading unit that provides the high current output. The PCU1-LT and PCU1-SP are ideally suited to primary current injection, stability testing and circuit breaker testing. In addition, the SP version offers direct-reading CT ratio and polarity tests and a 100A secondary injection output. T&R also offer the higher-powered PCU1-HP and PCU2.

Feature PCU1-LT PCU1-SP PCU1-HP PCU2  
Primary Injection Yes Yes Yes Yes  
Maximum Output Power 11.5kVA 11.5kVA 16.6kVA 20kVA  
Secondary Injection No Yes No No  
CT ratio/polarity test No Yes Yes No  

Two loading units are available, delivering a maximum output current of 2000A or 5000A. Each loading unit has three output taps to allow for a wide range of load impedances. For example, the NLU5000 may be configured to either give a maximum current of 5000A on the 2.3V range, 2500A on the 4.6V range or 1250A on the 9.2V range. Additional loading units are also available to order to meet customers requirements for stability testing.

The control units are rated at 11.5kVA with a 2 second overload capability of 23kVA using pulse mode. All metering is digital and a memory facility is provided to hold the current reading when the output trips or is switched off. The current is thyristor controlled and is automatically switched off when the device under test trips.

The PCU1 systems have a high accuracy timing system, allowing timing tests to be carried out to a resolution of 1ms. Selection for normally open or normally closed contacts is automatic, and the status of the contacts is shown on the front panel.

The PCU1 systems have a high accuracy timing system, allowing timing tests to be carried out to a resolution of 1ms. Selection for normally open or normally closed contacts is automatic, and the status of the contacts is shown on the front panel.

Timing modes are available to test under and over current devices, re-closers, under and over voltage devices, current trips and circuit breakers. A full range of high current output leads are available to complement the system in a range of lengths.
 

PUC1 Specifications

 

Accles & Shelvoke| Aqua-Tronics | Arbiter Systems | Clare Instruments | Haefely | Hipotronics | HV Diagnostics | Megger | Tettex | T & R Equipment  
Home Page | High Current | High Voltage | Cable Fault | Oil Test | Transformer | Insulation 

 
Macey's Electrical Pty Ltd
ABN 17 344 601 468
Unit 1, 49 Gavenlock Road,  Tuggerah,  Sydney  Australia  2259

 

Phone: 61 2 4353 4644 

Mobile: 0412 678 925

Fax: 61 2 4353 4424

mailto:sales@maceyselectrical.com.au
 

Copyright: 1978 to 2007                                                   Last update: Friday, 03 October 2008