T & R Test Equipment Model PT15-10s High Voltage Cable Test System.
  • Zero to 15kV DC output Voltage.
  • 10mA output capability.
  • Both voltage and current metered on HV output.
  • Automatic earth system for dumping capacitive loads.
  • HV output plug and socket.
  • Key operated supply switch to prevent unauthorized operation.
  • Zero-volt interlock.
  • Visual indication of test piece failure.
  • Compact unit with lightweight insulated case.

 

 

 

Product Description
T&R Test Equipment is a market leader in the field of protection test equipment. The range includes primary and secondary current injection equipment up 6000A, voltage sources, micro-ohmmeters and high voltage test systems up to 100kV.

The PT15-10s high voltage dc test set is designed to perform tests on installed cable and jointing systems. The unit has a zero to –15kVdc variable output with a maximum charging capability of 10mA. A zero-volt interlock is fitted that prevents the output being switched on unless the output control is at zero.

The unit includes an automatic load discharge system that discharges the cable under test when the output is switched off or a breakdown occurs. The internal dumping system can discharge a maximum of 1.25kJ, corresponding to 7.5µF at 15kV. A DP20 discharge probe is also supplied as standard with the PT15-10s, allowing cables with a capacitance of up to 12mF to be discharged at 15kV.

In the event of a test object failure, the overload circuit will automatically switch off the output voltage and earth the output via the internal discharge circuit. The output voltage is metered by a large, linear, analogue instrument marked 0-15kV. The current in the test object is metered by a second analogue instrument with 0-10 scale marking. The meter reads 0-10mA directly, or 0-1mA when the ÷10 push button is operated.

The HV output from the unit uses a high quality plug and socket system, allowing for easy cable replacement.

The PT15-10s is one of a range of high voltage test systems available from T&R. DC systems are available up to ±30kV and AC systems up to 100kV.

 

T and R unit KV100-100 High Voltage AC Test System 100kV/100mA.
Unit KV100-100  and          KV30-40

Unit Type

Voltage

Current

PT15-10s

-15kVdc 10mA

PT18-10

±18kV 10mA

PT30-10

±30kV 10mA

KV5-100

5kV 100mA

KV10-120

10kV 120mA

KV15-80

15kV 80mA

KV30-40

30kV 40mA

KV30-100

30kV 100mA

KV50-100

50kV 100mA

KV50-200

50kV 200mA

KV100-100

100kV 100mA
PT15-10s Specifications

Output
The output of the PT15-10S is by a partially screened high voltage cable connected to the set by a high voltage connector.

Unit Type Voltage Continuous 5 minutes  
PT15-10s 0 to 15kV 5mA 10mA  

The above intermittent on time must be followed by an off time of 15 minutes, and are based on an ambient
temperature of 25°C.

Metering
The output voltage on the PT15-10S is metered on the HV output by an analogue instrument.
 

Unit Type Range Accuracy  
PT15-10s 0 to 15kV ±1.5% of full scale  


The output current on the PT15-10S is metered by a dual range analogue instrument. The 1mA range is selected by the ÷10 pushbutton adjacent to the mA meter.

Unit Type Range Accuracy  
PT15-10s
 
10mA ±2.5% of full scale  
1mA ±2.5% of full scale  
 

Overload Protection
The PT15-10s is protected by an overload trip on the output that operates at 12mA.

Load Discharge System
The PT15-10S is fitted with an automatic internal load discharge system that grounds the load via a 10kW resistor when the output is switched off. The discharge system is rated to dissipate 1.25kJ every 15 minutes. A maximum load capacitance of 7.5mF may be discharged from 15kV.

The PT15-10S is also supplied with a DP20 manual discharge probe, rated to dissipate 3.6kJ every 15 minutes. The probe has a resistance of 30kW, and can discharge up to 12mF at 15kV.

 

Supply Requirements  
PT15-10s 110V±10% 50/60Hz 1ph 250VA max  
  230V±10% 50/60Hz 1ph 250VA max  

Protection and Safety
The output of the unit is protected by an overload trip, and the input and control supplies are protected by fuses.

The PT15-10S is designed to meet the requirements of BS EN61010.

An earth terminal is provided on the unit which must be connected to a low impedance local earth.

Temperature Range
Storage -20°C to 60°C,   Operating 0°C to 45°C

Dimensions
340mm (H) x 230mm (W) x 330mm (D)

Weight
11kg

Accessories supplied with Unit
Supply lead, spare fuse, operating manual, output lead, DP20 discharge probe, earth lead, shoulder strap.


 

Accles & Shelvoke| Aqua-Tronics | Arbiter Systems | Clare Instruments | Haefely | Hipotronics | HV Diagnostics | Megger | Tettex | T & R Equipment  
Home Page | High Current | High Voltage | Cable Fault | Oil Test | Transformer | Insulation 

 
Macey's Electrical Pty Ltd
ABN 17 344 601 468
Unit 1, 49 Gavenlock Road,  Tuggerah,  Sydney  Australia  2259

 

Phone: 61 2 4353 4644 

Mobile: 0412 678 925

Fax: 61 2 4353 4424

mailto:sales@maceyselectrical.com.au
 

Copyright: 1978 to 2007                                                   Last update: Friday, 03 October 2008