Overload Protection
The PT15-10s is protected by an
overload trip on the output that operates at 12mA.
Load Discharge System
The PT15-10S is fitted with an automatic internal load discharge
system that grounds the load via a 10kW resistor when the output
is switched off. The discharge system is rated to dissipate 1.25kJ
every 15 minutes. A maximum load capacitance of 7.5mF may be
discharged from 15kV.The PT15-10S
is also supplied with a DP20 manual discharge probe, rated to
dissipate 3.6kJ every 15 minutes. The probe has a resistance of
30kW, and can discharge up to 12mF at 15kV.
|
Supply Requirements |
|
|
PT15-10s |
110V±10% |
50/60Hz |
1ph |
250VA max |
|
| |
230V±10% |
50/60Hz |
1ph |
250VA max |
|
Protection and Safety
The output of the unit is protected by an overload trip, and the
input and control supplies are protected by fuses.
The PT15-10S is designed to meet the requirements of BS EN61010.
An earth terminal is provided on the unit which must be connected
to a low impedance local earth.
Temperature Range
Storage -20°C to 60°C, Operating 0°C to 45°C
Dimensions
340mm (H) x 230mm (W) x 330mm (D)
Weight
11kg
Accessories supplied with
Unit
Supply lead, spare fuse, operating
manual, output lead, DP20 discharge probe, earth lead, shoulder
strap. |